General
DGK-03 voltage control relays are designed to block three-phase loads malfunctions arising from network.
Usage and Working Principle
Make the connections of the device in accordance with connection scheme.
To Adjust High Voltage Set: Value checking the value of display on the left, adjust the desirable value of (u>) button . Once you move the button , set value will be displayed.
With the help of the button ,the adjustment is value of display on the left display. 4 seconds later, displayers show voltage values.
Once the device is energized, firstly the pre-adjusted set values are displayed and 2 seconds later voltage values appear. When R, S and T phases are between the adjusted voltage values, relay (Out) LED is on and contact (2-3) closed. If any between phase-phase is over high voltage set value, it holds for 3 seconds(fixed) and then relay (Out) LED is off, high voltage error (U>)LED is on and contact (2-3) opened. Whichever phase-phase voltage value is high, its display blinks, contact (2-3) opened. When voltage values declines 5V below set value, it holds for adjusted (t) knob time and then relay (Out) LED is on, high voltage error(U>) LED is off and contact (2-3) closed.
Maintenance
might damage the device. Make sure device works after cleaning
Warnings
Please use the device according to the manual.
Don't use the device in wet.
Include a switch and circuit breaker in the assembly.
Put the switch and circuit breaker nearby the device, operator can
reach easily.
Mark the switch and circuit breaker as releasing connection for device.
Specifications
Operating Voltage(Un)....: 3 x 380V AC
Operating Power...............: <6VA
High Voltage (U>)...........: 400V - 460V
Waiting (t).......................: 0,1sec - 10sec.
Display..................: 3x 3digit 9mm display and leds
Measurement Precision...: ±%1
Connection Type..............: Terminal connection
Contact....................:5A/250V AC (Resistive Load)
Cable Diameter.................: 2,5mm²
Weight................................: Max. 220gr.
Panel Hole Sizes................: 91x91mm
Mounting...........................: Vertical assembled in
the panel or assembled on the din rail
Operating Altitude..........: <2000meter
Power Source : AC
Theory : Voltage relay
is_customized : Yes
Contact Load : Low Power
Model Number : DGK-03
Voltage : 380V
Use : Protective
Protect Feature : Sealed
Protection Item 1 : Overvoltage